- Sectors
- Electronics
Cleanrooms for the electronics industry
ESD-safe areas for SMT assembly, wire bonding, optoelectronics, testing and packaging. Two protections in the same environment: from particulate according to ISO 14644 and from electrostatics according to IEC 61340-5-1.
- Double protection — ISO 14644 classification for particulate and IEC 61340-5-1 electrostatic management in the same environment
- The invisible threshold — a hundred volts destroy a CMOS; a person starts to feel a discharge at around three thousand
- Moisture-sensitive components — IPC/JEDEC J-STD-033: room at 40–50 % RH, dry storage below 5 %, floor life tracked per reel
- Light for inspection — LED with colour rendering CRI > 90, 750–1500 lux at the workstations, fixtures with no UV emission
- ISO 5–7Classes delivered for the sector
- IEC 61340-5-1Electrostatic management
- 22 ±2 °CStability for soldering profiles
- AuditAudit-ready documents, where required
Electronics manufacturers, contract manufacturers, research centres
They entrusted Phamm Engineering with their controlled-contamination environments, from design to qualification.
The class is written on the component
Not on the department and not on the process: on the smallest component that passes through. The limits are those of ISO 14644-1 for 0.5 µm particles.
- ISO 5≤ 3,520 part./m³
Optoelectronics and bonding
Alignment of laser diodes, photodiodes and image sensors, optical-fibre coupling, wire bonding: where the defect is not an interruption but a loss of performance that no electrical test detects.
Photonics · Wire bonding - ISO 6≤ 35,200 part./m³
High-density SMT
Soldering lines with 0201 and 01005 components, fine-pitch BGAs, flip-chip and hybrid modules. Particle control and electrostatic control active at the same time, not one after the other.
SMT · BGA · Flip-chip - ISO 7≤ 352,000 part./m³
Testing and packaging
Functional testing, burn-in, automated optical inspection, packaging in a controlled atmosphere and storage of moisture-sensitive components in low-humidity cabinets.
Test · AOI · MSD
Six problems that electronics brings and other sectors do not
Every item is a requirement with a number and a standard behind it. If a requirement has no measure, it is not a requirement.
One particle, two pads
Modern boards have pitches below 0.3 mm and microscopic pads. A single particle deposited between two pads becomes a solder bridge or a cold joint. In ISO 6–7 the concentration is reduced by a hundred to a thousand times compared with an industrial environment, and it is the only way to remove that defect from the statistics.
A single earth point
Conductive or dissipative floors with controlled resistivity between 10⁴ and 10⁹ Ω, work surfaces earthed through limiting resistors, bipolar ionisers over non-conductive surfaces: everything converges on a Common Point Ground. Construction materials are chosen not to generate triboelectric charges.
Extraction where the fumes arise
Ceiling filter coverage is 60–80 % with 30–60 air changes per hour, but the soldering machines need local extraction: fluxes evaporate where the operator is, and must be captured there, not diluted in the volume.
The floor life of every reel
Moisture-sensitive components are managed according to IPC/JEDEC J-STD-033: room at 40–50 % relative humidity to slow absorption, dry storage cabinets below 5 % for open reels, and exposure-time tracking for every reel. Once the limit is exceeded, the reel goes through bake-out, not the line.
Repeatable reflow profiles
The room temperature is held at 22 ±2 °C: this makes the reflow thermal profile repeatable, avoids thermal stress on components and maintains the accuracy of the vision systems, which are calibrated cold and work warm.
Light that does not lie
Visual inspection is a measurement operation, and it needs its own instrumentation: LED fixtures with colour rendering CRI > 90, illuminance between 750 and 1500 lux at the workstations and no ultraviolet emission, which would degrade photosensitive components.
The damage happens long before anyone feels it
A hundred volts are enough to destroy a CMOS component. A person begins to perceive a discharge at around three thousand. Between the two thresholds there is a factor of thirty, and inside that factor lie all the failures nobody saw coming: the part leaves the line working and fails in the field.
That is why an EPA area is not designed on feeling but on measurement: surface potential kept below a hundred volts, floor resistivity between 10⁴ and 10⁹ Ω, ionisers on surfaces that cannot be earthed, and quarterly instrumental verification. Compliance is demonstrated with a report, not with the absence of shocks.
- 100 VDestroy a CMOS component
- 3,000 VBefore a person feels it
- 10⁴–10⁹ ΩFloor resistivity
Six steps, one point of contact
It is the same path across all ten sectors: what changes is what we look at at each step, not who answers.
-
01
Analyse
Process, standards and site constraints: from these come the class and the URS that sets it.
-
02
Design
Layout, separate flows, pressure cascade and HVAC, verified on BIM and CFD models.
-
03
Manufacture
Panels, metalwork and switchboards in our workshop, with factory acceptance testing (FAT).
-
04
Install
On-site assembly, systems and monitoring, on-site verification (SAT) and start-up.
-
05
Qualify
We carry out the tests and deliver audit-ready documentation, where required.
-
06
Support
Scheduled maintenance, filters and calibration, even on systems by others.
Where our cleanrooms end up
Six areas with requirements that differ from one another: the class changes, the component’s sensitivity changes, the way of earthing it changes.
High-density SMT lines
Assembly of boards with 01005 and 0201 components, BGA and QFN, with precision placement and electrostatic control along the whole line.
ISO 6 · ESDWire bonding and flip-chip
Gold or aluminium wire interconnects and flip-chip bumping, with particle and thermal control for reliable joints over time.
ISO 5–6Optoelectronics and photonics
Assembly of laser diodes, photodiodes, SFP and QSFP modules and optical-fibre coupling, where contamination is a loss of signal.
ISO 5MEMS and imaging sensors
Packaging and testing of accelerometers, gyroscopes, pressure sensors and CMOS image sensors in an ultra-clean, ESD-safe environment.
ISO 5 · ESDPower electronics
Assembly of IGBT modules and silicon carbide and gallium nitride converters, with soldering in a controlled atmosphere.
ISO 6–7Testing and burn-in
Functional test, burn-in and screening rooms with stable temperature and humidity, because a result that cannot be repeated is not a result.
ISO 7
The regulatory framework we apply
Environmental classification, electrostatic management, moisture-sensitive components and assembly acceptability criteria. Ten documents, all applicable in the same cleanroom.
- ISO 14644-1:2015
- ISO 14644-3:2019
- IEC 61340-5-1
- IEC 61340-5-3
- ANSI/ESD S20.20
- IPC/JEDEC J-STD-033
- IPC J-STD-001
- IPC-A-610
- ISO 9001:2015
- IATF 16949
Cleanrooms for the electronics industry
The questions we receive most often from production and quality departments, with the short answer.
Why is a cleanroom needed to assemble electronic boards?
Because modern boards have pitches below 0.3 mm and pads measured in tens of micrometres. A single particle deposited on a pad becomes a solder bridge or a cold joint, and the defect shows up months later, in the field. In an ISO 6–7 cleanroom the particle concentration is reduced by a hundred to a thousand times compared with a standard industrial environment: that defect leaves the statistics instead of being chased with tests.
How is ESD protection integrated into the cleanroom?
At the structural level, not with accessories. Conductive or dissipative floors with controlled resistivity between 10⁴ and 10⁹ Ω, all work surfaces earthed through limiting resistors, bipolar air ionisers to neutralise charges on non-conductive surfaces and a common-point earthing system. The cleanroom’s construction materials are also selected not to generate triboelectric charges: one wrong panel defeats the network.
Which class is needed for an SMT line?
It depends on the smallest component that passes through. For a line with 0402 components and above, ISO 7 is adequate. For 0201 and 01005, fine-pitch BGAs or high-reliability modules you go up to ISO 6. For wire bonding and optoelectronic assembly ISO 5 is needed. The class is written on the component, not on the department.
How are moisture-sensitive components managed?
According to IPC/JEDEC J-STD-033. The room is kept between 40 and 50 % relative humidity to slow absorption, open reels go into dry storage cabinets below 5 %, and a system tracks the exposure time of every reel. If one exceeds its limit it does not go back on the line: it goes through a vacuum-oven bake-out, and only then returns.
Why is lighting a requirement and not a detail?
Because visual inspection is a measurement, and a measurement made with the wrong light is a wrong measurement. You need colour rendering CRI > 90 to tell a matt joint from a shiny one, between 750 and 1500 lux at the workstations depending on the type of inspection, and no ultraviolet emission, which degrades photosensitive components while they are being inspected.
What does the cost depend on?
On the class, the extent of the EPA area and its qualification, the presence of dry storage cabinets, the level of lighting required, local extraction at the soldering stations and integration with existing lines. An ISO 7 for testing and an ISO 5 for wire bonding are two different works. Describe the components and processes to us: we reply with a detailed quote.
Describe the components, not just the square metres
Size of the smallest component, soldering and bonding processes, electrostatic and moisture sensitivity, type of inspection. With these elements the quote is accurate first time, built on your process.
- IT+39 02 8364 7535
- ES+34 673 889 559
- info@phammeng.com
- Pozzo d’Adda (MI), Italy